Deluxe PLA140 Cassette Heat Pump

Large Room System // PLA-RP140BA

Our Deluxe PLA140 high performance cassette, has wide, powerful airflow, independent vane direction setting and wave airflow to provide consistent temperatures throughout the space you need to heat or cool. Perfect for larger residential rooms or office spaces. This model comes standard with an infrared remote controller.

Cooling Capacity14.0 kW
Heating Capacity16.0 kW

Features

Optimum Airflow

With the ability to independently control each wide vane’s airflow, these units are perfect for both residential and office environments, providing controlled airflow to all corners of the space you need to heat or cool. Advanced control of the vanes called “swing airflow” provides even greater heat distribution, periodically moving vanes up and down.

Automatic Air Speed Adjustment

This setting automatically adjusts the air-speed to match the conditions of the room. At the start of heating/cooling, the airflow is set to high-speed to quickly heat or cool the room and once the desired temperature is reached, it decreases for efficient operation.

High and Low Ceiling Modes

Our PLA cassettes are equipped to adjust the airflow volume to match the room height. This ensures that you get comfortable temperature control throughout the room no matter how high your ceiling.

Specifications

PLA-RP140BAR2 - Power Inverter Ceiling Cassette

· Function: Cooling/Heating · Type: Single Split, Inverter
· Capacity - Cooling: 14.0 kW · Capacity - Heating: 16.0 kW
· Capacity - Cooling (min. - max.): 6.2 - 15.3 kW · Capacity - Heating (min. - max.): 5.7 - 18.0 kW
· Power Input - Cooling: 4.55 kW · Power Input - Heating: 4.43 kW
· EER / COP: 3.08 / 3.61
· Operation Range - Cooling: -5 (-15*) / +46°C · Operation Range - Heating: -20 / +21°C
· Airflow (Lo-Mi1-Mi2-Hi, Litre/sec): 400 - 439 - 484 - 534 · Sound Level (Lo-Mi1-Mi2-Hi, dB(A)): 36 - 39 - 42 - 44
· Current Indoor - Cooling (Running): 1.07 A · Current Indoor - Heating (Running): 1.00 A
· Power Supply: 230V +/- 10% / Single Phase / 50 Hz · Refrigerant: R410A
· Liquid Pipe Size (OD, mm): 9.52 · Gas Pipe Size (OD, mm): 15.88
· Max. Pipe Length (m): 75 · Max. Pipe Height (m): 30
· Panel Dimensions (WxDxH, mm): 950 x 950 x 35 · Panel Weight: 6kg
· Dimensions (WxDxH, mm): 840 x 840 x 298 · Weight: 27 kg
· Note: Capacity ratings are based on the deluxe outdoor unit PUHZ-RP140VHA only. · [*]: -15°C in cooling when using an optional outdoor air outlet guide PAC-SG59SG-E.

PUHZ-RP140VKA2R1-A - DC Deluxe Inverter Outdoor Unit

· Function: Cooling/Heating · Type: Single Split or Multi Split, Power Inverter
· Multi-Split System Compatible: Yes (50:50) · Number of indoor units: 1, 2 or 3
· Capacity - Cooling: 13.0 kW · Capacity - Heating: 16.0 kW
· Capacity - Cooling (min. - max.): 6.2 - 15.3 kW · Capacity - Heating (min. - max.): 5.7 - 18.0 kW
· Operation Range - Cooling: -5 (-15*) / +46°C · Operation Range - Heating: -20 / +21°C
· Sound Level - Cooling (dB(A)): 50 · Sound Level - Heating (dB(A)): 52
· Airflow (Litre/sec): 2000 · Current - Cooling Outdoor (Rated / Max.): TBA / 28 A
· Current - Heating Outdoor (Rated / Max.): TBA / 28 A · Power Supply: 230V / Single Phase / 50 Hz
· Refrigerant: R410A · Liquid Pipe Size (OD, mm): 9.52
· Gas Pipe Size (OD, mm): 15.88 · Max. Pipe Length (m): 75
· Max. Pipe Height (m): 30 · Dimensions (WxDxH, mm): 1050 x 330(+30) x 1338
· Weight: 120 kg · [*]: -15°C in cooling when using an optional outdoor Air Protect Guide PAC-SH95AG-E.

·  Rating Conditions (AS / NZS 3823):
   Cooling – Indoor: 27°C DB, 19°C WB. Outdoor: 35°C DB.     Heating – Indoor: 20°C DB, Outdoor: 7°C DB, 6°C WB.

·  Sensible Cooling Conditions, Indoor: 27°C DB, 20°C WB. Outdoor: 35°C DB.

·  Dry function will not work when the room temperature is below 13°C.

·  Colour: Heat pump units shown may not be colour accurate, please ensure you view an actual unit for colour matching.

·  Maximum length is inclusive of height differential. i.e. (20m length/12m high) means the pipe can be 12m high and 8m across for a total length of 20m.

·  Measure of Energy Efficency: A calculated measurement of energy efficiency for both heating and cooling using the ratio of kW input to kW output.
   EER = Energy Efficiency Ratio
   COP = Coefficient of Performance
   AEER# = Annual Energy Efficiency Ratio
   ACOP# = Annual Coefficient of Performance
   #These include standby power in the rating calculation

·  Star Ratings based on the Seasonal Energy Rating standard for New Zealand - cold zone [GEMS 2019]

Downloads

Support

Optional

Optional Accessories

This automatic filter elevation panel is designed for easy filter cleaning. This feature enables filter lowering operation down to 4m at the press of a button.
Air outlet shutter plates used with Deluxe Cassette indoor units to blank off up to two air outlets.
This air outlet guide is used to force air vertically out of the outdoor unit, can be used to prevent the outdoor unit from short cycling the exhaust air. It also enables the outdoor unit to be mounted closer to a wall or other outdoor units and enables them to operate at -15°C in cooling mode.