Power Inverter Ducted / Ceiling-Concealed

PEA-RP140EA2

Ducted / ceiling-concealed indoor unit - inverter heat pump with wired PAR-21MAA 7 day wall timer. Cooling/Heating capacity: 14.0/16.0kW. (WxDxH, mm): 1415 x 690 x 428. Weight: 76kg. Liquid / Gas Pipe (OD, mm): 9.52 / 15.88. Requires a PUHZ-RP140VHA outdoor unit.

Discontinued Product

Specifications

· Function: Cooling/Heating · Type: Single Split, Inverter
· Capacity - Cooling: 14.0 kW · Capacity - Heating: 16.0 kW
· Capacity - Cooling (min. - max.): 6.2 - 15.3 kW · Capacity - Heating (min. - max.): 5.7 - 18.0 kW
· Power Input - Cooling: 4.83 kW · Power Input - Heating: 4.28 kW
· AEER - Cooling: 2.77 · ACOP - Heating: 3.56
· Operation Range - Cooling: -5 (-15*) / +46°C · Operation Range - Heating: -20 / +21°C
· Airflow (Lo-Hi, Litre/sec): 800-1000 · Sound Level (Lo-Hi, dB(A)): 51-55
· Current Indoor - Cooling (Running): 4.55 A · Current Indoor - Heating (Running): 4.55 A
· Power Supply: 230V +/- 10% / Single Phase / 50 Hz · Refrigerant: R410A
· Liquid Pipe Size (OD, mm): 9.52 · Gas Pipe Size (OD, mm): 15.88
· Max. Pipe Length (m): 75 · Max. Pipe Height (m): 30
· Dimensions (WxDxH, mm): 1415 x 690 x 428 · Weight: 76 kg
· External Static Pressure: 125 Pa · Note: Capacity ratings are based on the deluxe outdoor unit PUHZ-RP140VHA only.
· [*]: -15°C in cooling when using an optional outdoor air outlet guide PAC-SG59SG-E.

Support

*Actual price may differ.

Discontinued product