i-BX-N Fully Packaged Hot Water Heat Pump

i-BX-N 004M

Mitsubishi Electric Climaveneta has used the latest advancements in hot water heat pump technology to offer the i-BX-N fully packaged air to water heat pump. The highly efficient, low noise system fits seamlessly into both domestic and light commercial environments offering both hot water and space heating and cooling. The i-BX-N Range is low maintenance and easy to install, with minimal connections to make.

Discontinued Product

Features

Specifications

Function: Hot Water Heating
Type: Monobloc Air Source Heat Pump
Refrigerant Type: R410A
HEATING (A7/W35)*¹
Capacity [kW]: 4.63
Power Input [kW]: 1.51
COP: 3.07
HEATING (A7/W35)*2
Capacity [kW]: 4.62
COP: 3.12
COOLING (A35/W7)*3
Capacity [kW]: 4.20
Power Input [kW]: 1.55
EER: 2.71
COOLING (A35/W7)*4
Capacity [kW]: 4.20
EER: 2.76
OPERATING RANGE
Heating Operation Ambient Temperature [°C DB]: -20 to 45
Cooling Operation Ambient Temperature [°C DB]: 5 to 45
Heating Flow Temperature [°C]: 25 to 60
Cooling Flow Temperature [°C]*5: -8 to 18
HYDRONIC DATA
Water Pipe Size: 1" BSP Parallel Thread. ISO 228/1
Safety Valve [MPa (Bar)]: 0.6 (6)
Primary Pump: Yonos CS 6
Expansion Vessel [L]: 2
Precharge Pressure [MPa (Bar)]: 0.1 (1)
OPERATING CHARACTERISTICS
Sound Pressure Level at 1m [dBA]*¹: 50
Flow Rate [L/min]: 7.8 - 21
ELECTRICAL DATA
Power Supply: 230V / Single Phase / 50 Hz
Maximum Current [A]: 8
GENERAL
Dimensions (WxDxH) [mm]: 900 x 370 x 940
Weight [kg]: 80
Notes

*1 Under normal heating conditions at outdoor temp: 7°CDB / 6°CDB, outlet water temp 45°C, inlet water temp 40°C
*2 Under normal heating conditions at outdoor temp: 7°CDB / 6°CDB, outlet water temp 45°C, inlet water temp 40°C as tested to BS EN14511.
*3

Support

*Actual price may differ.